Start the engine via the main pump controller; the ECM will generate an overspeed signal and shutdown protecting both the engine and pump.
Engine Quick Search
Clarke brings touchscreen technology to JU4H Tier 3 engines with the TSP-E panel. Newly developed Touch Screen Panel for Electronic Engines (TSP-E) expands to JU6H and C13H Series Engines. Clarke's NSR Heat Exchanger makes field service quick and convenient. An Extra Year of Warranty Coverage just by maintaining your engine according to NFPA25!
o Start the engine via the main pump controller; the ECM will generate an overspeed signal and shutdown protecting both the engine and pump. EXAMPLE • Rated Speed: 1760 RPM • Overspeed Shutdown: 2024 RPM (115% of 1760 RPM) • Verification Shutdown: 1730 o The controller will indicate an alarm at interconnect terminal #3
Clarke C32H Operation And Maintenance Instruction Manual
View and Download Clarke C32H operation and maintenance instruction manual online. ELECTRONIC ENGINES FOR FIRE PUMP APPLICATIONS. C32H engine pdf manual download. Also for: C32h0-ufac10, C32h0-ufac18, C32h0-ufac20, C32h0-ufac28, C32h0-ufac30, C32h0-ufac38, C32h0-ufac40, C32h0-ufac48,...
This controller can be used to convert water pumps into automatic booster sets and provides 2 main functions: 1. It provides automatic operation of your pump. • This in-line device maintains water pressure from booster pumps by instantly sensing water usage and automatically starting or stopping the pump. 2. It protects the pump from running dry.
Clarke DP6H-UFAA50 Operation And Maintenance Instruction …
Most Clarke diesel engine fire pump drivers are heat exchanger cooled and some engines also have a charge air cooler (CAC) that uses raw water to cool the air before entering the intake manifold. Page 30: Cooling Loop
Clarke ZE Operation And Maintenance Instruction Manual
View and Download Clarke ZE operation and maintenance instruction manual online. FIRE PUMP APPLICATIONS. ZE engine pdf manual download. Also for: Zf, Ze4h-ufad60, Zf6h-ufaa60, Zf6h-ufac70.
• Mild steel enclosure construction with “Clarke Red” powder coat finish • Front hinged door for easy access to inside • Tested for electromagnetic compatibilty per CISPR 11
0C071963 Fire Alarm Control by CLARKE FIRE - Radwell …
0C071963 Fire Safety from CLARKE FIRE 2-Year Warranty, Radwell Repairs - , PC BOARD, MECHANICAL ENGINE CONTROL & ALARM BOARD, FIRE PUMP, SPEED SWITCH, STAND-OFF MOUNT
Clarke EPC2200 Booster Pump Electronic Control Unit
The EPC2200 Electronic Control Unit is an in-line electronic device designed to be used with booster pumps in order to maintain water pressure from the pumps by instantly sensing water usage & automatically starting the pump depending on demand.